    The EBW1 series intelligent air circuit breakers (ACB) are designed for AC 50Hz power systems with rated voltages of 400V and 690V, and rated currents ranging from 630A to 6300A.They are mainly used for power distribution and for protecting circuits and electrical equipment from overload, short circuit, undervoltage, and single-phase grounding faults.Equipped with an intelligent trip unit, the EBW1 ACB provides precise and selective protection, helping to prevent unnecessary power outages and ensuring a stable and reliable power supply.This series fully complies with IEC 60947-1&nbsp...
  • доля:
  • звяжыцеся з намі Інтэрнэт-запыт
  • WhatsApp:8613736779975

The EBW1 series intelligent air circuit breakers (ACB) are designed for AC 50Hz power systems with rated voltages of 400V and 690V, and rated currents ranging from 630A to 6300A.


They are mainly used for power distribution and for protecting circuits and electrical equipment from overload, short circuit, undervoltage, and single-phase grounding faults.


Equipped with an intelligent trip unit, the EBW1 ACB provides precise and selective protection, helping to prevent unnecessary power outages and ensuring a stable and reliable power supply.


This series fully complies with IEC 60947-1 and IEC 60947-2 standards.

Operating Conditions

Ambient temperature: -5°C to +40°C (average temperature within 24 hours not exceeding +35°C)

Altitude: ≤2000 m

Pollution degree: Class 3

Humidity: Relative humidity should not exceed 50% at +40°C; higher humidity levels are permissible at lower temperatures (up to 90% at +20°C).
When condensation occurs, appropriate protective measures should be taken.


Main technical parameter

Type
EBW1-2000EBW1-3200EBW1-6300
Pole
3P, 4P3P, 4P3P, 4P
Using category
BBB
Rated current InA630, 800, 1000 1250, 1600, 20002000, 2500, 30004000, 5000, 6300
Rated frequencyHz505050
Rated operation voltage UeV400, 690400, 690400, 690
Rated insulation voltage UiV800800800
Arcing distancemm000
Rated impulse withstanding voltage Uimp
V800080008000
Rated operation short circuit breaking capacity Ics (O-t-CO)400VkA5080100
690VkA405075
Rated limiting short circuit breaking capacity Icu (O-t-CO)400VkA80100120
690VkA506585
Rated short circuit closing capacity Icm400VkA176220264
690VkA105143187
Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S)400VkA506585
Operation lifePer hourtimes202010
Electricaltimes1000500500
Mechanicaltimes1000050005000
Full breaking time
ms20~3020~3020~30
Full closing time
ms55~7055~7055~70
Power consumption3PW36012002000
4PW45017502300
Resistance of each poleFixed typeμΩ119-
Draw out typeμΩ201410
Dimensions (L×W×H)3P fixed typemm362×323×402422×323×402
3P draw out typemm375×461×452435×471×452
4P fixed typemm457×323×402537×323×402
4P draw out typemm470×461×452550×471×452
Approximate weight3P fixed typekg4155
3P draw out typekg7195245
4P fixed typekg51.565-
4P draw out typekg86115260


Overload protection data

Overload protectionEBW1-2000~6300
Adjust scope Ir1
(0.4-1)In (pole difference 2%)
1.05 Ir1h≥2h non-tripping
1.3 Ir1h≤1h tripping
Delay time tr1 when current is 2.0 Ins3.32, 5.32, 8.00, 13.3, 20, 26.6, 33.3, 45, 60, 93.3, 133, 200, 266, 333, 400, 433
Delay time tr1 when current is 3.0 Ins1.25, 2, 3.5, 7.5, 10, 12.5, 16.8, 22.5, 35, 50, 75, 100, 125, 150, 162
Accuracy%±10



Short circuit, short time delay 
Adjust scope Ir1 Ir2(0.4-15)In (pole difference 2%)
Delay time tr2ms100, 200, 300, 400
Accuracy%±10


Electrical accessories

Under-voltage releaseRated working voltage Ue(V)AC400 AC230

1000A 3 pole ACB

Acting voltage (V)(0.35~0.7) Ue
Reliable close voltage (V)(0.85~1.1) Ue
Non close voltage (V)≤0.335Ue
Power loss12VA (EBW1-1000 5VA)

Shunt releaseRated control power voltage Us(V)AC400 AC230 DC220 DC110

1000A 3 pole ACB

Acting voltage (V)(0.7~1.1) Ue
Open time40VA 40W (EBW1-1000 5VA)
Power lossless than 30ms

Close electromagnetic ironRated control power voltage Us(V)AC400 AC230 DC220 DC110

1000A 3 pole ACB

Acting voltage (V)(0.85~1.1) Ue
Open time40VA 40W (EBW1-1000 5VA)
Power lossless than 70ms

Motor operating deviceRated control power voltage Us(V)AC400 AC230 DC220 DC110

1000A 3 pole ACB

Acting voltage (V)(0.85~1.1) Ue
Open time40VA 40W (EBW1-1000 5VA)
Power lossless than 5s

онлайн паведамленне

Калі ласка, увядзіце сапраўдны адрас электроннай пошты
код верыфікацыі Не можа быць пустым

Спадарожныя тавары

Contact Us

Phone: +8613736779975

E-mail: sales@vcbbreaker.com

Address: 66 Punan Road, Yueqing Economic Development Zone, Zhejiang, China

Аўтарскае права © Yangmei Electric Group, 2025  Усе правы абаронены

Карта сайта

Гэты вэб-сайт выкарыстоўвае файлы cookie, каб гарантаваць, што вы атрымаеце найлепшы вопыт на нашым сайце.

Прыняць адхіліць